Test results |
Related symptoms |
Probable cause |
Remedy |
Discharge (high) pressure abnormally high |
After stopping compressor, pressure drops to about 196 kPa (2.0 kgf/cm{sup 2}, 28 psi) quickly and then falls gradually. |
Air in system |
Discharge, evacuate (see page 21-94) and recharge with specified amount (see page 21-96). |
No bubbles in sight glass when condenser is cooled by water |
Excessive refrigerant in system |
Discharge, evacuate and recharge with specified amount. |
Reduced or no air flow through condenser |
- Clogged condenser or radiator fins
- Condenser or radiator fan not working properly
|
- Clean
- Check voltage and fan rpm.
- Check fan direction.
|
Line to condenser is excessively hot. |
Restricted flow of refrigerant in system |
Restricted lines |
Discharge pressure abnormally low |
Excessive bubbles in sight glass; condenser is not hot. |
Insufficient refrigerant in system |
- Check for leak.
- Charge system.
|
High and low pressures are balanced soon after stopping compressor. Low side is higher than normal. |
- Faulty compressor discharge valve
- Faulty compressor seal
|
Replace the compressor. |
Outlet of expansion valve is not frosted, low-pressure gauge indicates vacuum. |
- Faulty expansion valve
- Moisture in system
|
- Replace
- Discharge, evacuate and recharge with specified amount.
|
Suction (low) pressure abnormally low |
Excessive bubbles in sight glass; condenser is not hot. |
Insufficient refrigerant in system |
- Repair the leaks.
- Discharge, evacuate and recharge with specified amount.
- Charge as required.
|
Expansion valve is not frosted and low-pressure line is not cold. Low-pressure gauge indicates vacuum. |
- Frozen expansion valve (Moisture in system)
- Faulty expansion valve
|
- Discharge, evacuate and recharge with specified amount.
- Replace the expansion valve.
|
Discharge temperature is low and the air flow from vents is restricted. |
Frozen evaporator |
Run the fan with compressor off, then check evaporator temperature sensor. |
Expansion valve is frosted. |
Clogged expansion valve |
Clean or replace. |
Receiver/dryer outlet is cool and inlet is warm (should be warm during operation). |
Clogged receiver/dryer |
Replace |
Suction pressure abnormally high |
Low-pressure hose and check joint are cooler than the temperature around evaporator. |
Expansion valve open too long |
Repair or replace. |
Suction pressure is lowered when condenser is cooled by water. |
Excessive refrigerant in system |
Discharge, evacuate and recharge with specified amount. |
High and low-pressure are equalised as soon as the compressor is stopped and both gauges fluctuate while running. |
- Faulty gasket
- Faulty high-pressure valve
- Foreign particle stuck in high-pressure valve
|
Replace the compressor. |
Suction and discharge pressures abnormally high |
Reduced air flow through condenser. |
- Clogged condenser or radiator fins
- Condenser or radiator fan not working properly
|
- Clean
- Check voltage and fan rpm.
- Check fan direction.
|
No bubbles in sight glass when condenser is cooled by water |
Excessive refrigerant in system |
Discharge, evacuate and recharge with specified amount. |
Suction and discharge pressure abnormally low |
Low-pressure hose and metal end areas are cooler than evaporator. |
Clogged or kinked low-pressure hose parts |
Repair or replace. |
Temperature around expansion valve is too low compared with that around receiver/dryer. |
Clogged high-pressure line |
Repair or replace. |
Refrigerant leaks |
Compressor clutch is dirty. |
Compressor shaft seal leaking |
Replace the compressor. |
Compressor bolt(s) are dirty. |
Leaking around bolt(s) |
Tighten bolt(s) or replace compressor. |
Compressor gasket is wet with oil. |
Gasket leaking |
Replace the compressor. |